Euroka Embedded Power Subrack 36KW -48VDC and -57VDC
Non-Trade customers are welcome to purchase.
For Trade customers, please Sign In or Register for a Trade Account
You are submitting an enquiry for
The CBE-EPS36KW is an integrated power solution designed to transform AC power into DC power efficiently. It delivers a consistent voltage of -48 V and -57 V to equipment. This power system boasts a remarkable capacity of 36 kW, rendering it suitable for both new installations and the enhancement of existing sites through capacity expansion and reconstruction endeavours.
Features:
- Measurement Management: Track and report current, power, and energy usage for each circuit breaker.
- Autonomous Backup: Circuit breakers can function independently with various power modes (voltage, power, capacity, time), including scheduled operation and exemptions.
- Usage Control: Manage circuit breakers by designated usages like Customized Load, BLVD Load, LLVD1-4 Loads, and more.
- Adjustable Capacity: Users can customize circuit breaker capacity (3 A to rated capacity) according to load requirements.
- Temperature Protection: Intelligent circuit breakers trigger a high-temperature alarm and auto-shutdown in case of overheating.
- Remote Operation: Easily control circuit breakers remotely for power toggling.
Scenarios:
- Enterprise telecom scenario
Product Type |
CBE-EPS36KW |
|
System |
||
Dimension (W × D × H) |
442mm x 330mm x 5U |
|
Weight |
< 25kg (without rectifier module and packaging) |
|
Installation Mode |
19-inch rack |
|
Cabling Mode |
Front inlet, front outlet |
|
Maintenance Mode |
In front |
|
Height of Power Rack |
5U |
|
Number of Module Slots |
9 |
|
AC Distribution |
||
AC Input Module |
AIU03 |
AIU02 |
Input Mode |
Three phase compatible with single phase |
Dual live AC power |
Input Voltage |
Three phase compatible with |
85~300 VAC |
Input Frequency |
45Hz - 65Hz, rated value: 50Hz/60Hz |
|
Input Capacity |
1 x 100A/3P MCB |
1x125A/2P MCB |
SPD |
Nominal lightning strike discharge current 30kA (8/20μs) |
|
DC Distribution |
||
Output Voltage |
Normal mode: 42VDC - 58VDC, rated value: 53.5VDC |
|
Maximum Capacity |
Three phase: 36kW; single phase or dual live: 18kW |
|
Battery Branch |
6 × 125A/1P MCB |
|
LLVD |
2 × 125A MCB, 3 × 63A MCB (Circuit breaker usage can be customised) |
|
BLVD |
4 × 63A MCB, 2 × 32A MCB (Circuit breaker usage can be customised) |
|
SPD |
Nominal lightning strike discharge current: Differential mode - |